ANA AIRMAN SDG45S-8E2 36 kW 45 kVA Mobile Diesel Generator Package with Highway Trailer
Shipping Quote Required
Request a Shipping QuoteCouldn't load pickup availability
ANA AIRMAN SDG45S-8E2 36 kW 45 kVA Mobile Diesel Generator Package with Highway Trailer
The ANA AIRMAN SDG45S-8E2 45 kVA Mobile Diesel Generator Package delivers continuous three-phase and single-phase electrical output engineered for commercial construction jobsites, municipal utility bypass pumping, disaster relief operations, and critical emergency standby power. Driven by an EPA Tier 4 Final turbocharged 57.7 HP Isuzu 4LE2X liquid-cooled diesel engine, this mobile system provides 36 kW continuous prime power (38.8 kW maximum standby rating) while restricting operational noise down to an ultra-quiet 64 dB(A) at 23 feet.
Equipped with proprietary Delta Demand Excitation for high inductive motor-starting capacity and an electronic isochronous governor holding line frequency within ±0.25%, the SDG45S-8E2 automatically adjusts excitation to match heavy cyclical tool demand without terminal voltage drop. Featuring an internal 80.5-gallon fuel tank providing over 28.75 hours of runtime at full continuous load and mounted directly to a heavy-duty highway trailer (4,519 lbs GVWR), this turnkey power station provides immediate towing mobility and multi-day operation across demanding field environments.
Recommended Jobsite Applications
- Commercial Building & Infrastructure Projects: Supplying primary power to jobsite sub-distribution panels, structural welders, concrete saws, and multi-bank cordless tool charging stations.
- Municipal Utility & Bypass Dewatering: Delivering continuous 3-phase 208V, 240V, or 480V power to municipal trash pumps, submersible dewatering units, and sewer bypass equipment.
- Facility Emergency Standby: Providing automated 120/240V single-phase or three-phase emergency backup power to commercial refrigeration nodes and municipal maintenance facilities via auto-start integration.
- Live Event & Sound-Sensitive Operations: Supplying clean, stable voltage for concert lighting arrays, mobile broadcast studios, and nighttime urban street repairs requiring low 64 dB(A) acoustic limits.
Key Performance & Operational Features
- Tier 4 Final Isuzu 4LE2X Engine: 4-cylinder turbocharged diesel uses a DOC aftertreatment system requiring no DEF, simplifying field refueling logistics and reducing maintenance overhead.
- Delta Demand Excitation Technology: Automatically manages magnetic excitation levels to handle severe motor-starting inrush spikes, preventing terminal voltage drops during heavy inductive tool starts.
- Complete Highway Transport Trailer Package: DOT-certified single-axle trailer rated at 4,519 lbs GVWR equipped with highway-rated tires, a heavy-duty tongue jack, and multi-hitch coupler options.
- Multi-Voltage Distribution Selector: Lockable selector switch enables rapid manual reconfiguration across 3-phase 208V, 240V, 416V, and 480V, as well as single-phase 120V, 240V, and 277V circuits.
- Extended 80.5-Gallon Fuel Reservoir: Internal fuel cell delivers up to 28.75 hours of uninterrupted operation at 100% full continuous prime load and over 55 hours at 50% load.
- DSEGenset Digital Master Controller: Microprocessor-based digital system provides clear monitoring of line voltage, current amperage, frequency, engine diagnostic codes, and auto-start terminal integration.
- External Bulk Fuel Connections: Standard 3-way fuel selector valves and quick-connect external supply ports allow immediate hookup to auxiliary jobsite fuel cells for extended multi-week runs.
What's Included
- 1 × ANA AIRMAN 36 kW Mobile Diesel Generator (MPN: SDG45S-8E2)
- 1 × Factory-Installed Isuzu 4LE2X Tier 4 Final Turbocharged Diesel Engine (57.7 HP)
- 1 × Heavy-Duty Single-Axle Highway Transport Trailer (4,519 lbs GVWR)
- 1 × DSEGenset Digital Auto-Start / Auto-Stop Microprocessor Controller
- 1 × Integrated 80.5-Gallon Internal Steel Fuel Cell with Fluid Containment
- 1 × External 3-Way Auxiliary Fuel Connection Port Assembly
- 1 × Complete Engine & Generator Technical Documentation Manual Set
Technical Specifications
| Specification Parameter | Product Detail |
|---|---|
| Manufacturer Brand | ANA AIRMAN |
| Model Part Number (MPN) | SDG45S-8E2 |
| Mobility Configuration | Single-Axle Highway Transport Trailer Package Included |
| Prime Continuous Power Rating | 36.0 kW (45.0 kVA) Continuous @ 1,800 RPM (3-Phase) |
| Standby Emergency Power Rating | 38.8 kW (48.5 kVA) |
| Engine Make & Displacement | Isuzu 4LE2X (2.2L / 133 cu in, 4-Cylinder Turbocharged) |
| Engine Emissions Certification | EPA Tier 4 Final & CARB Certified (DOC System; No DEF Required) |
| Gross Engine Mechanical Output | 57.7 HP (43.0 kW Mechanical Output @ 1,800 RPM) |
| Acoustic Sound Level | 64 dB(A) @ 23 Feet (Full 100% Prime Load) |
| Three-Phase Voltage Selection | 208V, 240V, 416V, 480V (Switchable) |
| Single-Phase Voltage Selection | 120V, 240V, 277V (Switchable) |
| Three-Phase Continuous Amps | 119A @ 208V | 108A @ 240V | 54A @ 480V |
| Single-Phase Continuous Amps | 60A × 2 @ 120V | 60A @ 240V |
| Fuel Reservoir Capacity | 80.5 Gallons (304.7 Liters Diesel) |
| Continuous Full-Load Runtime | 28.75 Hours @ 100% Load (2.80 gal/hr) | >55 Hours @ 50% Load |
| Trailer Rating (GVWR) | 4,519 lbs GVWR (Single-Axle Highway Transport Trailer) |
| Generator Dimensions (L × W × H) | 74.8" L × 38.2" W × 61.4" H (Generator Unit Only) |
| Trailer Package Dimensions (L × W × H) | 144.0" L × 70.0" W × 73.0" H (With Trailer) |
| Total Package Operating Weight | Dry: 2,954 lbs | Wet Generator: 3,337 lbs | Wet Package w/ Trailer: 3,923 lbs |
💡 MOTOR STARTING & RUNTIME SIZING TIP: The SDG45S-8E2 utilizes Delta Demand Excitation to stabilize transient voltage drop during high inductive inrush events. When sizing branch circuits for commercial pumps or compressor motors, utilize three-phase 240V or 480V distribution to reduce conductor sizing requirements and maintain the 28.75-hour full-load runtime of the 80.5-gallon fuel cell.
Frequently Asked Questions: ANA AIRMAN SDG45S-8E2
A: The SDG45S-8E2 is powered by an industrial Isuzu 4LE2X 2.2-liter 4-cylinder turbocharged liquid-cooled diesel engine producing 57.7 HP at 1,800 RPM and complying with EPA Tier 4 Final standards using a maintenance-free DOC system requiring no DEF.
A: It includes a lockable multi-voltage selector switch supporting three-phase 208V, 240V, 416V, and 480V, along with single-phase 120V, 240V, and 277V service at 60 Hz.
A: With its onboard 80.5-gallon fuel cell, the generator delivers approximately 28.75 hours of continuous operation at 100% full continuous prime load (2.80 gal/hr) and over 55 hours at 50% load (1.45 gal/hr).
A: Delta Demand Excitation provides automatic magnetic flux adjustments to absorb instantaneous motor-starting inrush spikes, preventing terminal voltage sag when cycling heavy inductive compressors and submersible pumps.
A: Yes. This complete mobile package includes a factory-matched single-axle highway transport trailer rated at 4,519 lbs GVWR with DOT-compliant running gear and interchangeable hitch coupler options.